Network
Network requirements for DataTalk — delay and packet loss limits for Ethernet and LTE, ports that must not be blocked, myACCESS outgoing connection, and how to test the network.
On this page
Reliable network communication is crucial for the trouble-free operation of DataTalk. A long delay or lost packets result in read and write errors on PLCs and cause problems with the connection to myACCESS.
Limits
| Interface | Network delay | Lost packets |
|---|---|---|
| Ethernet | below 10 ms | below 0.5 % |
| LTE | below 500 ms | below 1 % |
Ethernet
If the delay or packet loss is higher:
- Check the cabling and the switch.
LTE
If the delay or packet loss is higher:
- Check the LTE antenna, or replace it with a higher-gain version.
- Do not keep the antenna inside a steel cabinet.
- Try another operator.
- Try switching from LTE to 3G.
How to test the network
Use the ping command against the PLC or another device on the network and look at the response times and the lost packets in the summary:
ping <IP address of the PLC>
To test a specific TCP port on Windows, use:
Test-NetConnection -ComputerName <IP address> -Port <port>
The result must contain TcpTestSucceeded : True.
Ports
| Port | Purpose | What to check |
|---|---|---|
| 80 (HTTP), 443 (HTTPS) | web interface of DataTalk — default values | must not be used by another application; can be changed in DataTalk Manager → Web Server |
| 4840/TCP | OPC UA — default port | must not be blocked by the firewall, see PLC communication fails — OPC UA |
| port of the myACCESS server | outgoing connection of myACCESS — the port is in the client.conf file of the myACCESS configuration | the outgoing port must be allowed in the firewall, see myACCESS Troubleshooting |
Several network cards
If the computer has several network cards — for example Ethernet to the machines and Wi-Fi to the internet — the card with the internet connection must be the preferred one (the lowest interface metric on Windows). WSL binds to the preferred interface; if that interface has no DNS or internet connection, myACCESS cannot connect. See myACCESS Troubleshooting.